Top
power-system

Voltage Drop Calculator (IEC 60364 & NEC NFPA 70)

Voltage drop calculator with a single page covering BOTH IEC 60364-5-52 Annex G (metric mm² cables, A/B limits) and NEC NFPA 70 Chapter 9 Tables 8–9 (AWG / kcmil, 3% branch / 5% feeder FPNs). Copper / aluminium, 1-phase / 3-phase / DC, temperature correction, parallel conductors, conduit material (NEC), reactance X and ampacity cross-check.

#voltage-drop-calculator#iec-60364-voltage-drop#nec-voltage-drop-calculator#nec-chapter-9-table-9#awg-kcmil-voltage-drop#mm²-cable-voltage-drop

Switch between IEC metric (mm², metres, Annex G A/B limits) and NEC imperial (AWG / kcmil, feet, 3%/5% FPN recommendations).

IEC 60364-5-52 · Annex G

Voltage Drop Calculator

Metric cable sizes. Enter the circuit, get the drop in volts and percent, checked against the IEC limit.

V

Line to neutral · typical 1φ 230 V

A

IB, not the breaker rating

≈ 12 AWG

m

One way, not the loop

cosφ

0.8 if you don't know it

Advanced
mΩ/m

0.08 is the default when no cable data is available

A

Derated value from IEC 60364-5-52 Annex B or the cable datasheet

2.37%
Within the limit
Drop
5.46 V
Voltage at load
224.5 V
Permitted
5.00 %
Power lost
135 W

Calculated with the Annex G method: resistivity in service taken as 1.25 × the value at 20 °C. Ampacity, protection and fault withstand are separate checks.

Author

Zakaria El Intissar

Electrical Engineer

Electrical engineer with 12+ years of experience in power systems. I create practical electrical calculators and standards-based technical guides that engineers can apply immediately in their daily work.

LinkedIn

Overview

Excessive voltage drop can cause motors to overheat, lights to dim, and protective devices to misbehave. Most standards (IEC 60364-5-52, NEC NFPA 70, HD 60364…) cap the drop at around 3 to 5 percent of the nominal voltage depending on whether the circuit is a feeder or a final sub-circuit.

Use the IEC / NEC toggle at the top of the tool to switch between the two standard families: the IEC 60364 (Annex G) tab works with metric mm² cross-sections, lengths in metres, and the classic A / B drop limits (with a distance bonus for runs longer than 100 m). The NEC NFPA 70 (Chapter 9) tab uses AWG / kcmil conductor sizes, lengths in feet, Chapter 9 Tables 8–9 impedance at your power factor, and the traditional 3% branch / 5% feeder FPN benchmarks for guidance.

Before specifying a cable, always run this check against the cross-section chosen by ampacity. Very often the cable sizing tool will recommend a larger size than ampacity alone because of long distance.

How it works

  1. 1. Pick the standard family
    Use the IEC 60364 / NEC NFPA 70 toggle at the top of the tool to switch between metric (mm², metres) and North-American (AWG/kcmil, feet) input units.
  2. 2. Define the system
    DC, single-phase or three-phase and the nominal voltage (230 V, 120/240 V, 277/480 V… whatever applies to your circuit).
  3. 3. Set line and load
    Current A, length, cross-section or AWG size, cos φ for AC, and material (Cu/Al). In NEC mode also pick conduit and coating; in IEC mode set the Annex G installation class.
  4. 4. Read drop % vs the allowed limit
    IEC result is compared against Annex G classes A/B with optional >100 m allowance. NEC result is compared against the 3% branch / 5% feeder FPN guidance. Iterate the size if needed.

FAQ

What is the allowed voltage drop?+

IEC 60364-5-52 Annex G uses classes A (3% lighting / 5% other) and B (6% / 8%), with a distance bonus for runs >100 m. NEC FPNs (non-enforceable guidance) recommend ≤ 3% on branch circuits and ≤ 5% total feeder + branch.

Do you include reactance?+

The IEC tab lets you set X mΩ/km (default 0.08) and the NEC tab reads effective impedance (R · cos φ + X · sin φ) from Chapter 9 Table 9 at the actual power factor. For very long or HV cables reactance matters most.

Should I use line-neutral or line-line voltage?+

Enter the nominal as labelled. For three-phase systems (both IEC and NEC) the calculator applies the √3 factor internally to derive the line-drop formula.

Are NEC voltage-drop limits enforceable?+

No — voltage drop in NEC is Fine-Print Note (FPN) guidance, not enforceable text. Local jurisdictions or project specifications often tighten or enforce them anyway.

Why metres vs feet / mm² vs AWG?+

IEC is metric (mm², metres) and is used in EU, Africa, ME, APAC. NEC uses AWG / kcmil and feet (North America). The toggle at the top switches the input units and the whole calculation recipe.

Why feet instead of metres in NEC?+

NEC NFPA 70 is written in imperial; lengths are traditionally entered in one-way feet and the per-run 2·L or √3·L factor is applied to obtain the full loop or three-phase drop.